DV-300 Adjustable Speed Drives
——— FUNCTION DESCRIPTION ———
6
21
T current ref 1
1st current reference value as a percentage of the Full load curr . The maximum value
possible depends on the Enable overload parameter.
Enable overload
disabled
T current ref 1
100% max
Enable overload
enabled
T current ref 1
200% max
T current ref 2
2nd current reference value as a percentage of the Full load curr . The maximum value
possible depends on the Enable overload parameter.
Enable overload
disabled
T current ref 2
100% max
Enable overload
enabled
T current ref 2
200% max
T current Ref
Total current reference value as a percentage of the Full load curr value.
The total current reference value consists of the signed addition of T current ref 1 and T current Ref 2.
Example 1:
T current ref 1 = +50%
T current ref 2-= +30%
T current ref = 50% + 30% = 80%
Example 2:
T current ref 1 = +40%
T current ref 2 = -60%
T current ref = 40-60% = -20%
The current reference value has an upper limit.
0 ... 10 V, 0 ... 20 mA and 4 ... 20 mA signals can be used when setting the reference value via terminals.
Reference set using input current, usually are with sign positive and they are used with biquadrant drives.
6.5 LIMITS
6.5.1 Speed Limits
LIMITS
Speed limits
Speed amount
[1]
Speed min amount [FF]
[2]
Speed max amount [FF]
Speed min/max
[5]
Speed min pos [FF]
[3]
Speed max pos [FF]
[6]
Speed min neg [FF]
[4]
Speed max neg [FF]
Parameter description
No.
Value
Standard
Configuration
min
max
Factory
American
Factory
European
Speed min amount [FF]
1
0
232-1
0
0
-
Speed max amount [FF]
2
0
232-1
5000
5000
-
Speed min pos [FF]
5
0
232-1
0
0
-
Speed max pos [FF]
3
0
232-1
5000
5000
-
Speed min neg [FF]
6
0
232-1
0
0
-
Speed max neg [FF]
4
0
232-1
5000
5000
-
Speed limited
Speed not limited (0)
Speed limited (1)
372
0
1
*
* This function can be assigned to a programmable digital output.