Yaskawa MEMOCON GL120 User Manual
Page 95
4.3 CPU Modules
— 4-39 —
Item
Specifications
Timers
1) Timing method:
Increment method
2) Types:
ON-delay, OFF-delay
3) Number of timers:
2,457 timers max.
4) Timer unit and ranges
Name
Unit
Range
1-s Timer
0.1-s Timer
0.01-s Timer
0.001-s Timer
1 s
0.1 s
0.01 s
0.001 s
1 to 65535 s
0.1 to 6553.5 s
0.01 to 655.35 s
0.001 to 65.535 s
5) External setting:
Possible
6) Power interruption preservation: Possible
Counters
1) Types:
Up Counter, Down Counter
2) Number of counters:
2,457 counters max.
3) Counting range:
1 to 65,535
4) External setting:
Possible
5) Power interruption preservation: Possible
Maximum Capacity of Data
Register
1) When the number of coils and relays is the default value, the following condition
must be met:
(Number of holding registers) + (Number of constant registers) + (Number of link
registers) ≤ 25,998
2) The maximum value of each reference can be freely set within the above limit from
the Programming Panel (Unit: word (1 word = 16 bit)).
Register
Setting range
Setting unit
Defaults
Example 1
Example 2
Holding
registers
1 to 25,995
1
9,999
19,854
25,995
Constant
registers
1 to
2
4,096
1
4,096
4,096
1
Link
registers
0 to
2
4,096
1,024
2,048
2,048
0
Memory Back-up
D
Back-up range:
1) Program memory
2) Data memory
D
Backup method
1) One lithium battery
2) five year warranty on battery (25 _C)
D
Back-up time
The total memory back-up time is 1 year (25 _C)
4