Yaskawa MEMOCON GL120 User Manual
Page 415

Installation and Wiring
5.3.3 Wiring Digital I/O Modules cont.
— 5-58 —
Example 2: Load Driving Power Supply for 100/200 VAC 16-point Output Module
Load driving power
supply(single-phase,
100/200 VAC, 50/60 Hz)
Fuse
Load
Fuse
Load
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Common 1-1
Common 1-2
Output 9
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
Common 2-1
Common 2-2
Figure 5.2 Load Driving Power Supply
B. DC Power Supply Specifications
1) As shown in Examples 1 and 2 later in this section, it is necessary to supply external DC
power (12/24 VDC) to the I/O Modules listed in the following table to power input signals
and drive loads:
Table 5.9 Digital I/O Modules Requiring External DC Power Supply
Name
Model No.
External Power Supply Specifications
12/24-VDC 16-point
Input Module
JAMSC-120DDI34300
Rated voltage: 12/24 VDC
Maximum permissible voltage: 30 VDC
12/24-VDC 32-point
Input Module
JAMSC-120DDI35400
Maximum permissible voltage: 30 VDC
Standard operating range:
Minimum ON voltage: 9 VDC
12/24-VDC 64-point
Input Module
JAMSC-120DDI36400
Minimum ON voltage: 9 VDC
Maximum OFF voltage: 5 VDC
5