System Components: Functions and Specifications
— 4-300 —
4.10 Rack-to-rack I/O Cables
This section describes the appearance, application, models and specifications of the
Rack-to-rack I/O Cables.
1) Appearance
Shielded cable
Model name
Connector 1
Connector 2
2) Applications
Rack-to-rack I/O Cables are used to connect two Expander Modules between two adja-
cent Racks.
3) Models and Specifications
The models and specifications of the Rack-to-rack I/O Cables are shown in the following
table.
Table 4.120 Models and Specifications of Rack-to-rack I/O Cable
Item
Specifications
Model Name
W0100-02
W0100-05
W0100-10
W0100-50
Model No.
JZMSZ-120W0
100-02
JZMSZ-120W0
100-05
JZMSZ-120W0
100-10
JZMSZ-120W0
100-50
Length (L)
0.2 m
0.5 m
1.0 m
5.0 m
Approx. Mass
80 g
100 g
150 g
450 g
Cable Specifications
26-core shielded cable, equivalent to UL20276, 0.08 mm
2
(AWG 28).
Connector Specifications
10126-6000EL + 10326-A500-00 (3M)
Connector 1 and connector 2 have the same specifications.
4) Application
a) More than one Rack-to-rack I/O Cable can be used at the same station; however, the
following conditions must be met:
(1) A maximum of 3 can be used.
(2) The total length of cables must not exceed 6.0 m.
4