Yaskawa MEMOCON GL120 User Manual
Page 455
6.2
I/O Modules
— 6-17 —
2) 200-to 240-VAC 16-point Input Module
Table 6.5 Specifications of the 200-to 120-VAC 16-point Input Module
Item
Specification
Name
200- to 240-VAC 16-point Input Module
Model Name
AC200IN-16P
Model No.
JAMSC-120DAI74309 (EN standards)
Rated Voltage
200 to 240 VAC
Maximum Allowable Voltage
264 VAC
Rated Frequency
50/60 Hz
Allowable Frequency Range
47 to 63 Hz
Inrush Current
320 mA
Rated Current
7 mA (at 200 VAC, 50 Hz)
Input Impedance
28.6 kΩ (at 200 VAC, 50 Hz)
23.1 kΩ (at 200 VAC, 60 Hz)
Standard Operating Ranges
ON voltage range: 159 to 264 VAC
OFF voltage range: 40 VAC max.
Input Type
AC type 2 (according to IEC1131-2)
Input Delay Times
OFF to ON: 20 ms max.
ON to OFF: 35 ms max.
Number of Commons
2
Number of Inputs per Common
8 points/common
Input Power Supply per Common
Different power supply phases cannot be connected for
each common.
External Connections
Removable terminal block with M3 screw terminals
Number of Inputs
16
Input Signal Indication
Indicator for each point; lit when input is ON.
Status saved in internal logic.
Status Indication
ACTIVE: Lits during input processing
Insulation Method
Photocoupler
Dielectric Strength
1,500 VAC for 1 min or 1,800 VAC for 1 s between input
terminals and internal circuits and between all input
commons
Insulation Resistance
100 MΩ min. (room temperature and humidity) between
input terminals and ground (via 500-VDC insulation
resistance meter)
External Power Supply
200 to 240 VAC supplied to signals
Derating Conditions
None
Internal Current Consumption
90 mA max. at 5 VDC (with all points ON)
Maximum Heating Value
3.5 W
Hot Swapping (Removal/Insertion
under Power)
Permitted
Approximate Mass
250 g
External Dimensions
40.3 x 130 x 103.9 mm (W x H x D)