4.3 CPU Modules

— 4-93 —

(4) The COMR instruction can be used for the MEMOBUS ports of the following Commu-

nications Module: Remote I/O Receiver Module.

The following tables summarizes the communications functions of the MEMOBUS ports on
the CPU10 Module.

Port

Communications Functions

Slave

C

i

i

Master Communications (COM Instructions)

Communications

COMM

COMR

MEMOBUS port 1

Supported.

Not supported.

Not supported.

MEMOBUS port 2

Supported.

Supported.

Not supported.

3. Toggle Switch

1) The toggle switch is a non-self-returning switch with the three setting positions shown in

the following diagram (left: RUN, center: NOM, right: PRT).

2) The toggle switch is used for the following two functions.

• Turning ON/OFF memory protection

• Entering RUN operation

a) Memory Protection

The toggle switch can be used to turn ON/OFF memory protection to prevent/allow
changes to the user program and other data from a programming device, such as a
Programming Panel or personal computer. Set the toggle switch to the required posi-
tion as described in the following table.