System Components: Functions and Specifications

4.4.11 M-NET Module cont.

— 4-184 —

Item

Specification

Communications Ports

S

ifi

i

Number of Ports

2

Specifications

Communications

Method

Half-duplex, start-stop synchronization

Transmission Level

Conforms to RS-422

Media (Transmission

Medium)

JKEV-SB 0.75 mm

2

x 2P:

Polyethylene-insulated cable with copper braid shield

Note JKEV-SB conforms to the specifications of the Japa-

nese Electric Wire and Cable Makers’ Association.

Baud Rate

9.6, 19.2, 38.4, or 57.6 Kbps

Number of Stations

15 Slaves max.

Station Address

1 to 15

Note 1 to 7 when B1086 and B2806 are used as Slaves

Transmission Distance Up to 1 km (total length)
Data Format

Transmission between Master and Slave is in the following

data format:

1) Start bits:

1

2) Data bit length:

7

3) Parity check:

Yes

4) Parity:

Even

5) Stop bits:

1

Transmission Error

Detection

Detects vertical parity (even parity)
Detects horizontal parity (even parity)

Transmission Mode

T Mode

Y Mode

Number of Digital

Transmission

Points

Input points:

256

Output points:

256

Input points:

256

Output points:

256

Number of

Register

Transmission

Points

Input registers:

0

Output registers: 0

Input registers:

15

Output registers: 15

Error Measures

(RAS)

Automatic removal and

recovery function for error

stations: None

Automatic removal and

recovery function for error

stations: Yes

Insulation Method

Photocoupler

External Connection

Removable terminal block with M3 screw terminals

4. Using M-NET Modules

1) Number of Modules

a) Communications between M-NET Modules are performed using I/O references, such

as input relays, output coils, input registers, and output registers. Therefore, I/O must
be allocated for the slot to which the M-NET Module is mounted according to the fol-
lowing rules.

4