Installation and Wiring
5.3.3 Wiring Digital I/O Modules cont.
— 5-62 —
Table 5.10 I/O Signal Cable Size
Name
Model No.
I/O Signal Cable Size
100-VAC 16-point Input Module
JAMSC-120DAI54300
0.5 mm
2
(AWG20) to 1.3 mm
2
(AWG16)
200-VAC 16-point Input Module
JAMSC-120DAI74300
(
)
(AWG16)
12/24-VDC 16-point Input
Module
JAMSC-120DDI34300
0.2 mm
2
(AWG24) to 0.8 mm
2
(AWG18)
100/200-VAC 8-point Output
Module
JAMSC-120DAO83000 0.5 mm
2
(AWG20) to 1.3 mm
2
(AWG16)
100/200-VAC 16-point Output
Module
JAMSC-120DAO84300 0.5 mm
2
(AWG20) to 1.3 mm
2
(AWG16)
Common cable: 1.3 mm
2
(AWG 16)
or larger
12/24-VDC 8-point Output
Module
JAMSC-120DDO33000 0.2 mm
2
(AWG24) to 0.8 mm
2
(AWG18)
12/24-VDC 16-point Output
Module (sinking)
JAMSC-120DDO34310
(
G 8)
12/24-VDC 16-point Output
Module (sourcing)
JAMSC-120DDO34320
Relay Contact 16-point Output
Module
JAMSC-120DRA84300 1) AC loads
0.5 mm
2
(AWG20) to 1.3 mm
2
(AWG16)
Common cable: 1.3 mm
2
(AWG
16) or larger
2) DC loads
0.2 mm
2
(AWG24) to 0.8 mm
2
(AWG18)
3) M3 Phillips screws are used in the external connection terminals. Accordingly, solderless
terminals for M3 Phillips screws may be used for terminals on the I/O Module end of I/O
signal cable.
4) When using an insulation transformer, always make sure to separate the primary and the
secondary coils. When using a noise filter, also be sure to separate the primary and the
secondary coils.
B. 32-point Digital I/O Module
1) There are 2 32-point Digital I/O Modules with connectors for external connections.
a) 12/24-VDC 32-point Input Module (Model No.: JAMSC-120DDI34300)
b) 12/24-VDC 32-point Output Module (Model No.: JAMSC-120DDO34310)
2) To connect to these Digital I/O Modules, use of the following I/O signal cables.
a) I/O Module cables manufactured by the user
b) Yaskawa W0300 32-point I/O Module Cables
5