System Components: Functions and Specifications
4.4.3 Remote I/O Receiver Module
— 4-112 —
If a status error occurs, the READY indicator will go off and the RMT ERR indicator will flash
as described in the following table.
Type of Error
RMT ERR Indication
ROM error
RMT ERR will flash continuously.
RAM error
RMT ERR will flash twice, go off for 1 s, and then repeat the cycle.
ASIC error
RMT ERR will flash three times, go off for 1 s, and then repeat the cycle.
Watchdog timer error
RMT ERR will flash four times, go off for 1 s, and then repeat the cycle.
2. Function
The Remote I/O Receiver Module functions as a slave station in a Remote I/O System
using coaxial cable as the transmission cable.
3. Specifications
The specifications of the Remote I/O Receiver Module are shown in the following table.
Table 4.46 Specifications of Remote I/O Receiver Module
Item
Specifications
Model Name
RIOR-COAX
Model No.
JAMSC-120CRR13100
Internal Current Consumption
800 mA
Maximum Heating Value
4.0 W
Hot Swapping (Removal/Insertion
Under Power)
Permitted
Approximate Mass
300 g
External Dimensions
Width:
1
40.3 mm
Height: 130 mm
Depth: 103.9 mm
Remote I/O Port Specifications
Topology
(Communications
Network)
Bus
Media Access Control
Method
Multi-drop (1: n communications)
Media
(Transmission Medium)
Coaxial cable (75Ω)
Modulation Method
Base band
Encoding Method
Manchester code
Baud Rate
Choose from 0.5/1/2/4 Mbps
Transmission Distance
Transmission distance varies according to the baud rate
and specifications of coaxial cable. If, for example, the
baud rate is 4 Mbps and 12C-5AF Coaxial Cable is used,
it is possible to transmit up to 1 km max.
Number of Stations
15 max. (Up to 15 Remote I/O Receiver Modules can be
connected)
Error Measures (RAS)
Automatic parallel off and malfunctioning station recovery
Synchronization Method
Frame
Communications Format
Conforms to HDLC.
Insulation Method
Pulse transformer
Connector
BNC connector