Yaskawa MEMOCON GL120 User Manual
Page 71
![background image](https://www.manualsdir.com/files/819912/content/doc071.png)
4.2 Power Supply Modules
— 4-15 —
2) The following figure and tables show an example of a Power Supply Module selection.
Slot No.
Rack 1
The total of the
maximum internal
current consumption of
all Modules is 6,820 mA
Rack 2
The total of the
maximum internal
current consumption of
all Modules is 1,990 mA
Rack 1
Slot
Name
Current Consumption
1
Power Supply Module PS10 (7 A)
---
2
pp y
(
)
3
CPU Module CPU20 (16 KW)
930 mA
4
(
)
5
MEMOBUS Module (RS-232)
600 mA
6
Remote I/O Driver Module
800 mA
7
PC Link Module
800 mA
8
Four-axis Motion Module
1650 mA
9
10
Four-axis Motion Module
1650 mA
11
12
Expander Module
390 mA
Rack 2
Slot
Name
Current Consumption
1
Power Supply Module PS05 (3A)
---
2
12/24-VDC 16-point Input Module
100 mA
3
12/24-VDC 16-point Input Module
100 mA
4
12/24-VDC 16-point Input Module
100 mA
5
12/24-VDC 16-point Input Module
100 mA
6
12/24-VDC 16-point Input Module
100 mA
7
12/24-VDC 16-point Output Module
220 mA
8
12/24-VDC 16-point Output Module
220 mA
9
12/24-VDC 16-point Output Module
220 mA
10
12/24-VDC 16-point Output Module
220 mA
11
12/24-VDC 16-point Output Module
220 mA
12
Expander Module
390 mA
4