4.4 Communications Modules
— 4-149 —
Item
Specifications
PC Link Port Specifications
Topology
(Communications
Network)
Bus
Media Access Control
Method
Token passing (n:n communications)
Media (Transmission
Medium)
Coaxial cable (75Ω)
Modulation Method
Base band
Encoding Method
Manchester code
Baud Rate
Choose from 0.5/1/2/4 Mbps
Transmission Distance
Transmission distance varies according to the baud rate
and specifications of the coaxial cable. If, for example,
the baud rate is 4 Mbps and a 12C-5AF Coaxial Cable is
used, it is possible to transmit up to 1 km max.
Number of Stations
32 stations max.
A total of 32 PC Link Modules can be connected,
including the local one.
Error Measures (RAS)
Automatic parallel off and malfunctioning station
recovery
Synchronization Method
Frame
Communications Format
Conforms to HDLC.
Insulation Method
Pulse transformer
Connector
BNC connector
MEMOBUS Port Specifications
Communications Method
Half-duplex stop-start synchronization
p
Transmission Levels
Conform to RS-232C
Protocol
MEMOBUS protocol
Baud Rate
9,600 bps (fixed)
Communications Mode
RTU mode
Data Format
1) Data bit length:
8
2) Parity check:
Yes
3) Parity:
Even
4) Stop bits:
1
Slave Address
Between 1 and 32. The station address of the PC Link
Module is the MEMOBUS slave address.
Transmission Distance
15 m (Can be extended to 4.5 maximum by using
Yaskawa modem.)
Transmission Error
Detection
CRC-16
Connector
D-sub connector (9-pin, female)
4