beautypg.com

Yaskawa MEMOCON GL120 User Manual

Page 205

background image

4.4 Communications Modules

— 4-149 —

Item

Specifications

PC Link Port Specifications

Topology

(Communications

Network)

Bus

Media Access Control

Method

Token passing (n:n communications)

Media (Transmission

Medium)

Coaxial cable (75Ω)

Modulation Method

Base band

Encoding Method

Manchester code

Baud Rate

Choose from 0.5/1/2/4 Mbps

Transmission Distance

Transmission distance varies according to the baud rate

and specifications of the coaxial cable. If, for example,

the baud rate is 4 Mbps and a 12C-5AF Coaxial Cable is

used, it is possible to transmit up to 1 km max.

Number of Stations

32 stations max.

A total of 32 PC Link Modules can be connected,

including the local one.

Error Measures (RAS)

Automatic parallel off and malfunctioning station

recovery

Synchronization Method

Frame

Communications Format

Conforms to HDLC.

Insulation Method

Pulse transformer

Connector

BNC connector

MEMOBUS Port Specifications

Communications Method

Half-duplex stop-start synchronization

p

Transmission Levels

Conform to RS-232C

Protocol

MEMOBUS protocol

Baud Rate

9,600 bps (fixed)

Communications Mode

RTU mode

Data Format

1) Data bit length:

8

2) Parity check:

Yes

3) Parity:

Even

4) Stop bits:

1

Slave Address

Between 1 and 32. The station address of the PC Link

Module is the MEMOBUS slave address.

Transmission Distance

15 m (Can be extended to 4.5 maximum by using

Yaskawa modem.)

Transmission Error

Detection

CRC-16

Connector

D-sub connector (9-pin, female)

4

This manual is related to the following products: