Yaskawa MEMOCON GL120 User Manual
Page 453

!
6.2
I/O Modules
— 6-15 —
2) Connecting to Field Wiring Terminals
Make sure to use M3 crimp terminals (round type) that are appropriate for the size of
the wire. Put insulation covers at each crimp when connecting to the field wiring termi-
nals as shown in the figure below.
Insulation cover
Make sure that the minimum clearance for air circulation is provided on both sides of
each crimp terminal by checking that the terminals are parallel to the barriers between
the terminals.
Crimp terminal
Barrier
Parallel to
barriers
Caution
When wiring to terminal blocks, always use crimp terminals on the cable ends. Using bare
wires may result in an electric shock or a short circuit if the wires become loose.
3) Protective Fuse
When using the Output Module, connect the fuse to the circuit to protect the output
circuit. Use a fuse with a current rating of 2a or less, which meets the specifications
described in IEC1272, Sheet2.
Recommended fuse: 217000 Series (made by Littlefuse)
6