beautypg.com

Yaskawa MEMOCON GL120 User Manual

Page 193

background image

4.4 Communications Modules

— 4-137 —

3. Specifications

The specifications of the MEMOBUS Module (RS-422) are shown in the following table.

Table 4.58 Specifications of MEMOBUS Module (RS-422)

Item

Specifications

Model Name

MEMOBUS-RS422

Model No.

JAMSC-120NOM27100

External Dimensions

Width: 40.3 mm

Height: 130 mm

Depth: 103.9 mm

Approximate Mass

300 g

Internal Current Consumption

600 mA

Maximum Heating Value

3.0 W

Hot Swapping

(Removal/Insertion Under

Power)

Permitted

MEMOBUS Port Specifications

Communications Method

Half-duplex stop-start synchronization

p

Transmission Levels

Conform to RS-422.

Protocol

MEMOBUS protocol or any other protocol

Baud Rate

19,200/9,600/7,200/4,800/3,600/2,400/2,000/

1,800/1,200/600/300/150 bps

Communications Mode

RTU mode or ASCII mode

Data Format

Transmission between the master and slaves uses the

following data format:

1) Data bit length:

8 (RTU mode) or 7 (ASCII mode)

2) Parity check:

Yes or No

3) Parity:

Odd or even

4) Stop bits:

1 or 2

Transmission Distance

500 m max.

Transmission Error

Detection

CRC-16 (RTU mode) or LRC (ASCII mode)

Connector

D-sub connector (9 pin, female)

4. Using MEMOBUS Modules (RS-422)

1) Number of Modules

Together with MEMOBUS Modules (RS-232) explained in 4.4.5 MEMOBUS Modules
(RS-232)
, two MEMOBUS Modules (RS-422) can be used.

2) Installation Location

The MEMOBUS Module (RS-422) can be mounted to any slot of the Mounting Base of
any Rack of the local channel. It will occupy one slot.

4

This manual is related to the following products: