241 — 3. specifications – Yaskawa MEMOCON GL120 User Manual
Page 297
![background image](https://www.manualsdir.com/files/819912/content/doc297.png)
4.6 Special Purpose Modules
— 4-241 —
3. Specifications
1) Hardware Specifications
The following table shows the hardware specifications of the Pulse Catch Module.
Table 4.99 Hardware Specifications of Pulse Catch Module
Item
Specifications
Voltage Used
12 VDC
24 VDC
Name
Pulse Catch and Counter Module
Module Name
COUNTER-16CH
Model No.
JAMSC-120RDI34400
Rated Voltage
12/24 VDC
Maximum Permissible
Voltage
30 VDC
Input Type
Sourcing/sinking
Rated Current
5.0 mA
10.5 mA
Input Impedance
2.2 kΩ
Standard Operating
Range
Minimum ON Voltage:
9 VDC
Maximum OFF Voltage: 5 VDC
Input Type
Does not conform to JIS B 3501.
DC type 2 according to JIS B
3501.
Number of Commons
1
Input Points per Common
16 points per common
External Connections
40-pin connector: 1
Connector model: FCN-365P040 (made by Fujitsu Ltd.)
Input Points
16 points (when using pulse catch and counter functions together)
Input Signal Indicators
Light for each point that is ON, internal logic
Isolation Method
Photocoupler isolation
External Power Supply
For signals: 12 VDC
For signals: 24 VDC
Derating Conditions
None
Internal Current
Consumption
5 VDC, 200 mA (when all points are ON)
Maximum Heating Value
6 W
Hot Swapping
Permitted.
Approximate Mass
300 g
External Dimensions
40.3 ¢ 130.0 ¢ 103.9 mm (W x H x D)
4