beautypg.com

Yaskawa MEMOCON GL120 User Manual

Page 100

background image

System Components: Functions and Specifications

4.3.3 Specifications of CPU Modules cont.

— 4-44 —

Item

Specifications

Program Memory Capacity

32K words (1 word: 24 bits)

Maximum I/O Points

1) Digital I/O points: 4,096 points max. (1 point: 1 bit)

2) I/O registers: 512 registers max. (1 register: 16 bits)

3) Local I/O:

D

Number of channels: 1

D

Number of Racks: 4 Racks max. including CPU Rack.

D

Number of mountable I/O Modules: 54 Modules max.
The total number of points/registers including all remote input/output points must
meet the above conditions 1 and 2.

4) Remote I/O:

D

Number of channels: 2

D

Number of stations per channel: 15

D

Number of Racks per channel: Max. 4 Rack

D

Number of I/O points per station:
(Digital input points ÷ 8) + (Input registers x 2) ≤ 512 bytes

(Digital output points ÷ 8) + (Output registers x 2) ≤ 512 bytes

The total number of points/registers including all remote input/output points must
meet the above conditions 1) and 2).

Maximum points of coils and

relays

1) When the number of data registers is the initial value, the following condition must

be met:
(Number of coils) + (Number of relays) ≤ 65,520

2) The maximum value of each reference can be freely set within the above limit from

the Programming Panel (Unit: point (1 point = 1 bit)).

Coil/Relay

Setting range

Setting unit

Defaults

Example 1

Example 2

Coils

16 to 65,472

16

8,192

57,328

65,472

Link coils

0 to

6

4,096

1,024

2,048

2,048

0

MC coils

0 to

65,

512

256

512

512

0

MC control

coils

0 to

65,

320

160

320

320

0

Input relays

16 to 65,472

16

1,024

4,096

16

MC relays

0 to

65,

512

256

512

512

0

MC control

relays

0 to

65,

512

256

512

512

0

M code

relays

0 to

65,

192

96

192

192

0

Note: Number of I/O allocatable input relays = 4096 − (Number of output coils which

have been allocated)

4

This manual is related to the following products: