4.2 Power Supply Modules
— 4-11 —
2. Specifications of PS05 (Model No. JRMSP-120CPS11100)
PS05 specifications are shown in the following table.
Table 4.4 Specifications of PS05
Item
Specifications
Input
Rated Voltage
100/200 VAC (Selectable)
p
Permissible Voltage Range
85 to 132 VAC or 170 to 264 VAC
Rated Frequency
50/60 Hz
Permissible Frequency
Range
47 to 63 Hz
Permissible Momentary Pow-
er Interruption Time
Less than one cycle. However, momentary power
interruption intervals must be more than 1 s.
Wave Distortion Factor
10% or less
Power Consumption
1) At 100 VAC: 60 VA max.
2) At 200 VAC: 75 VA max.
Current Leakage
1) At 132 VAC: 1.4 mA max.
2) At 264 VAC: 2.8 mA max.
Inrush Current
1) At 132 VAC, cold start: 25 A max.
2) At 264 VAC, cold start: 50 A max.
No. of Phases
Single-phase
Output char-
i i
Permissible Voltage Range
5.1 VDC
p
acteristics
Rated Current
3.0 A
Fuse
Standard fusing glass tube fuse (250 VAC, 2 A)
Field Wiring Terminals
1) Equipped with three kinds of terminals: field
wiring terminals (AC1, AC2), filter ground
terminal (ACG), and protective ground terminal
(FG).
2) M4 Phillips screws are used in each terminal.
3) Use wire size 1.5 mm
2
(AWG16) to 2.5 mm
2
(AWG13) to connect terminals.
Hot Swapping
(Removal/Insertion Under Power)
Not permitted
Maximum Heating Value
10 W
Approximate Mass
350 g
External Dimensions
Width:
1
40.3 mm
Height:
130 mm
Depth:
103.9 mm
4