System Components: Functions and Specifications
4.4.12 YENET 1600-D Module cont.
— 4-192 —
3) Installation Location
a) A YENET 1600-D Module can be mounted to any slot of the Mounting Base of any
Rack. It will occupy one slot.
b) The following diagram shows where to mount a YENET 1600-D Module.
Example
PS05:
Power Supply Module (3 A)
CPU20:
CPU Module (16 KW)
YENET:
YENET 1600-D Module
DI:
12/24-VDC 16-point Input Module
DO:
12/24-VDC 16-point Output Module
MB12:
12-slot Mounting Base
DI
PS
05
DO
DI
M
P
MB12
Slot No.
Rack 1 (CPU Rack)
CPU20
1
2
3
4
5
6
7
8
9
10
11
12
YE-
NET
DO
Local channel
DI
YE-
NET
YE-
NET
YE-
NET
Figure 4.56 Mounting YENET 1600-D Modules
4) Communications Port
A YENET 1600-D master can use the communications port to communicate with up to 63
YENET 1600-D slaves or other slave devices conforming to DeviceNet at a baud rate of
500 kbps. The transmission distance depends on the baud rate used. If, for example, the
baud rate is 500 kbps, it is possible to transmit up to 100 m.
4
A
EXAMPLE
"