System Components: Functions and Specifications

4.4.12 YENET 1600-D Module cont.

— 4-192 —

3) Installation Location

a) A YENET 1600-D Module can be mounted to any slot of the Mounting Base of any

Rack. It will occupy one slot.

b) The following diagram shows where to mount a YENET 1600-D Module.

Example

PS05:

Power Supply Module (3 A)

CPU20:

CPU Module (16 KW)

YENET:

YENET 1600-D Module

DI:

12/24-VDC 16-point Input Module

DO:

12/24-VDC 16-point Output Module

MB12:

12-slot Mounting Base

DI

PS

05

DO

DI

M

P

MB12

Slot No.

Rack 1 (CPU Rack)

CPU20

1

2

3

4

5

6

7

8

9

10

11

12

YE-

NET

DO

Local channel

DI

YE-

NET

YE-

NET

YE-

NET

Figure 4.56 Mounting YENET 1600-D Modules

4) Communications Port

A YENET 1600-D master can use the communications port to communicate with up to 63
YENET 1600-D slaves or other slave devices conforming to DeviceNet at a baud rate of
500 kbps. The transmission distance depends on the baud rate used. If, for example, the
baud rate is 500 kbps, it is possible to transmit up to 100 m.

4

A

EXAMPLE

"