beautypg.com

Yaskawa MEMOCON GL120 User Manual

Page 130

background image

System Components: Functions and Specifications

4.3.4 Using CPU Modules 1 (For CPU20, CPU30, and CPU35) cont.

— 4-74 —

5) Setting Pins 1 and 2

a) Pins 1 and 2 are used to determine communications parameters. Set them to meet

the requirements of your system.

Table 4.23 Setting Communications Parameters for MEMOBUS Port

Pin 1

Pin 2

Function

ON

OFF

Sets communications mode of MEMOBUS port to RTU and sets the

communications parameters for the MEMOBUS port to the RTU mode

defaults shown below:

1) Slave address: 1

2) Baud rate:

9,600 bps

3) Parity check

Yes

4) Parity:

Even

5) Stop bits:

1

6) Data bit length:

8

7) Delay time:

0 ms

ON

Sets communications mode of MEMOBUS port to ASCII and sets the

parameters for the MEMOBUS port to the ASCII mode defaults shown

below:

1) Slave address:

1

2) Baud rate:

2,400 bps

3) Parity check:

Yes

4) Parity:

Even

5) Stop bits:

1

6) Data bit length:

7

7) Delay time:

0 ms

OFF

Any

Enables the user to define and set the communications mode and

communications parameters for the MEMOBUS port through

programming devices (Programming Panel, personal computer, etc.) .

4