Yaskawa MEMOCON GL120 User Manual
Page 458

Low Voltage Directives
6.2.4 Specifications of the I/O Module cont.
— 6-20 —
5) Relay Contact 16-point Output Module
Table 6.8 Specifications of the Relay Contact 16-point Output Module
Item
Specification
Name
Relay Contact 16-point Output Module
Model Name
RELAY-16P
Model No.
JAMSC-120DRA84309 (EN Standards)
Contact specifications
240 VAC, 1 A, resistive load
Rated Voltage/Current
24 VDC, 1 A, resistive load
Maximum Load Power
750 VA (AC loads)
90 W (DC loads)
Maximum Load Voltage
264 VAC/125 VDC
Minimum Load
Voltage/Current
100 m VDC, 0.1 mA
Contact Resistance
100 mΩ max.
Contact Life
Electrical
3 A at 30 VDC, resistive load: 100,000 operations min.
1 A at 30 VDC, resistive load: 300,000 operations min.
τ = 7 ms:
150,000 operations min.
τ = 40 ms: 40,000 operations min.
1 A at 120 VAC, cosφ = 1.0: 400,000 operations min.
cosφ = 0.4: 250,000 operations min.
1 A at 240 VAC, cosφ = 1.0: 300,000 operations min.
cosφ = 0.4: 200,000 operations min.
Mechanical
20 million operations min.
Output Delay Times
OFF to ON: 10 ms max.
ON to OFF: 15 ms max.
Output Type
Relay contact outputs
Number of Commons
2
Number of Outputs per Common 8 points/common
Output Power Supply per
Common
Connect Power supplies to the same phases to each common
for 100 to 120 VAC or 200 to 240 VAC.
Do not connect both an AC power supply and a DC power
supply to one module at the same time.
External Connections
Removable terminal block with M3 screw terminals
Output Protection Type
Unprotected outputs (according to IEC 1131-2)
Built-in Fuse
None
Surge Suppressor
None
Other Output Protection
None
Number of Outputs
16
Output Signal Indication
Indicator for each point; lits when output is ON.
Status saved in internal logic.
Status Indication
ACTIVE: Lits during output processing.
Insulation Method
Relay
Dielectric Strength
1,500 VAC for 1 min or 1,800 VAC for 1 s between output
terminals and internal circuits and between all output
commons.
Insulation Resistance
100 MΩ min. (room temperature and humidity) between output
terminals and ground (via 500-VDC insulation resistance
meter)
External Power Supply
100 to 120 VAC or 200 to 240 VAC or 24 VDC supplied to
drive loads