Low Voltage Directives

6.2.4 Specifications of the I/O Module cont.

— 6-20 —

5) Relay Contact 16-point Output Module

Table 6.8 Specifications of the Relay Contact 16-point Output Module

Item

Specification

Name

Relay Contact 16-point Output Module

Model Name

RELAY-16P

Model No.

JAMSC-120DRA84309 (EN Standards)

Contact specifications

240 VAC, 1 A, resistive load

Rated Voltage/Current

24 VDC, 1 A, resistive load

Maximum Load Power

750 VA (AC loads)
90 W (DC loads)

Maximum Load Voltage

264 VAC/125 VDC

Minimum Load

Voltage/Current

100 m VDC, 0.1 mA

Contact Resistance

100 mΩ max.

Contact Life

Electrical

3 A at 30 VDC, resistive load: 100,000 operations min.
1 A at 30 VDC, resistive load: 300,000 operations min.

τ = 7 ms:

150,000 operations min.

τ = 40 ms: 40,000 operations min.

1 A at 120 VAC, cosφ = 1.0: 400,000 operations min.

cosφ = 0.4: 250,000 operations min.

1 A at 240 VAC, cosφ = 1.0: 300,000 operations min.

cosφ = 0.4: 200,000 operations min.

Mechanical

20 million operations min.

Output Delay Times

OFF to ON: 10 ms max.
ON to OFF: 15 ms max.

Output Type

Relay contact outputs

Number of Commons

2

Number of Outputs per Common 8 points/common
Output Power Supply per

Common

Connect Power supplies to the same phases to each common

for 100 to 120 VAC or 200 to 240 VAC.

Do not connect both an AC power supply and a DC power

supply to one module at the same time.

External Connections

Removable terminal block with M3 screw terminals

Output Protection Type

Unprotected outputs (according to IEC 1131-2)

Built-in Fuse

None

Surge Suppressor

None

Other Output Protection

None

Number of Outputs

16

Output Signal Indication

Indicator for each point; lits when output is ON.

Status saved in internal logic.

Status Indication

ACTIVE: Lits during output processing.

Insulation Method

Relay

Dielectric Strength

1,500 VAC for 1 min or 1,800 VAC for 1 s between output

terminals and internal circuits and between all output

commons.

Insulation Resistance

100 MΩ min. (room temperature and humidity) between output

terminals and ground (via 500-VDC insulation resistance

meter)

External Power Supply

100 to 120 VAC or 200 to 240 VAC or 24 VDC supplied to

drive loads

6