1.2

Precautions

— 1-15 —

Power Supply Noise Reduction

• Prevent noise from penetrating into the product by installing an isolation transformer or

a noise filter for the external power supply.

Noise from power supply may result in the malfunctioning of GL120 and GL130.

Select, Separate, and Lay External Wiring Correctly

• I/O lines connecting external devices to the 120-series I/O Modules must be selected

based on the following considerations: mechanical strength, resistance to noise, wiring
distance, signal voltage, etc.

• I/O lines must be separated from power lines both inside and outside the control panel

to minimize the affects of noise. Faulty operation may result if I/O lines are not sufficient-
ly separated from power lines.

Example of external wiring separation

Power lines

General control

circuit cables

Control panel separator

Digital I/O

signal cables

Analog I/O

signal cables

Pulse input

signal cables