Yaskawa MEMOCON GL120 User Manual
Page 457

6.2
I/O Modules
— 6-19 —
4) 100-to 120-VAC or 200-to 240-VAC 8-point Output Module
Table 6.7 Specifications of the 100-to 120-VAC or 200-to 240-VAC 8-point Output Module
Item
Specification
Name
100- to 120-VAC or 200- to 240-VAC 8-point Output Module
Model Name
ACOUT-8P
Model No.
JAMSC-120DAO83009 (EN Standards)
Rated Voltage
100 to 120 VAC or 200 to 240 VAC
Allowable Voltage Range
80 to 264 VAC
Rated Frequency
50/60 Hz
Allowable Frequency Range
47 to 63 Hz
Maximum Load Current
1.0 A rms/point
Output Voltage Drop
1.0 V rms
Output Delay Times
OFF to ON: 5 ms max.
ON to OFF: 1/2 cycle + 5 ms max.
OFF Leakage Current
3 mA max. at 240 VAC, 50 Hz
Minimum Load Current
10 mA rms
Output Type
Triac outputs
Number of Commons
8 (Each output circuit is independent.)
Output Power Supply per Common Possible to connect different power supply phases to the
commons.
External Connections
Removable terminal block with M3 screw terminals
Output Protection Type
Unprotected outputs (according to IEC 1131-2)
Built-in Fuse
None
Surge Suppressor
Varistor
Other Output Protection
None
Number of Outputs
8
Output Signal Indication
Indicator for each point; lit when output is ON.
Status saved in internal logic.
Status Indication
ACTIVE: Lights during output processing
Insulation Method
Phototriac
Dielectric Strength
1,500 VAC for 1 min or 1,800 VAC for 1 s between output
terminals and internal circuits and between all output circuit.
Insulation Resistance
100 MΩ min. (room temperature and humidity) between
output terminals and ground (via 500-VDC insulation
resistance meter)
External Power Supply
100 to 120 VAC or 200 to 240 VAC supplied to drive loads
Derating Conditions
None
Internal Current Consumption
150 mA at 5 VDC (with all points ON)
Maximum Heating Value
9.0 W
Hot Swapping
(Removal/Insertion Under Power)
Permitted
Approximate Mass
300 g
External Dimensions
40.3 x 130 x 103.9 mm (W x H x D)
6