4.3 CPU Modules
— 4-83 —
b) Setting examples of pins 1 and 2 are shown below:
(1) When DIP switch pins 1 and 2 are set as shown in the dia-
gram on the right, the communications parameters of ME-
MOBUS port are set to the RTU mode defaults shown below:
Communications mode: RTU
Communications parameters:
Slave address: 1
Baud rate:
9,600 bps
Parity check:
Yes
Parity:
Even
Stop bits:
1
Data bit length: 8
Delay time:
0 ms
(2) When connecting the Programming Panel to the CPU Module, the communica-
tions parameters must match the above values (except the delay time).
6) Setting Pin 3
a) When pin 3 is turned ON, the CPU Module will change to bridge mode. In this mode, a
MEMOBUS master connected to a MEMOBUS port on the CPU Module runs commu-
nications between communications devices on the MEMOBUS PLUS network.
b) In bridge mode, MEMOBUS master must use the node address set for the MEMO-
BUS PLUS port to specify the communications partner on the network. Refer to fol-
lowing information on the rotary switches for the setting. In bridge mode, the slave
address set for the MEMOBUS port is invalid.
4
A
EXAMPLE
"
1
234567
8
O N