4.3 CPU Modules
— 4-25 —
LED
Color
Indication when ON
READY
Green
CPU Module is normal.
RUN
Green
CPU Module is running.
MB+/ERR
Green
MEMOBUS PLUS port is transmitting/receiving
data normally.
Red
Transmitting/receiving error has occurred in
MEMOBUS PLUS port.
BAT ALM
Red
Voltage in the built-in battery in CPU Module is
running down.
ACTIVE
Green
Access to CPU Module from other Module is
possible.
TX/ERR
Green
MEMOBUS port is transmitting data normally.
/
Red
Transmitting/receiving error has occurred in
MEMOBUS port.
RX
Green
MEMOBUS port is receiving data normally.
MEM PRT
Green
Key switch has selected memory protect ON.
Figure 4.8 Appearance of CPU20
Note
Replace the battery in the CPU Module within two weeks after the BAT ALM indicator lights
(replacement battery: BR-2/3A-1).
Programs or data stored in the CPU Module or Motion Modules will be lost if replacement is
delayed.
4
RUN
READY
120 CPU 341 00
MB+/ERR
BAT ALM
ACTIVE
TX/ERR
RX
MEM PRT
LED area