Yaskawa MEMOCON GL120 User Manual
Page 328

System Components: Functions and Specifications
4.7.4 Two-axis Motion Module cont.
— 4-272 —
c) Based on the limits to the number of I/O references above, the maximum number of
Two-axis Motion Modules that can be used depends on the CPU Module, as shown
below.
Maximum Number of Two-axis Motion Modules that Can Be Used
CPU Module
Input Relays
and
Output Coils
Input
Registers and
Output
Registers
Max. No. of
MC15
Modules
Remarks
CPU20
CPU21
1,024
512
8
D
All input relays and
output coils will be used
for the MC15 Modules.
D
There will be 64 unused
I/O registers
CPU30
CPU35
4,096
512
16
D
There will be 2,944
unused input relays and
output coils.
D
There will be 8 unused
I/O registers.
Note
(1) When using Remote Stations, the limit is 8 Modules for the CPU20 and CPU21 and 12
Modules for the CPU30 and CPU35
(2) When using a PS10 or PS11 Power Supply Module, a single Two-axis Motion Module
uses 750 mA of the 7 A current available, so a maximum of 9 Modules can be used per
Rack.
2) Installation Locations
a) The Two-axis Motion Module requires one slot and can be mounted as shown below.
(1) If not using the absolute position detecting function, the Module can be mounted
to any slot on any Rack.
(2) If using the absolute position detecting function, the Module can be mounted to
any slot on the Mounting Base of the CPU Rack.
4