4.4.8 Uniwire Interface Module

— 4-160 —

If an error occurs either in the Module or in the Uniwire System, the READY, ERR1, ERR2 and
ERR3 indicators will operate as follows:

Type

Error

READY

ERR1

ERR2

ERR3

Remarks

Module

error

ROM error

Not lit

Lit

Not lit

Not lit

Checked when

power is turned

error

RAM error

Not lit

Not lit

Lit

Not lit

power is turned

ON.

Internal watchdog timer

error

Not lit

Not lit

Not lit

Lit

Checked all the

time.

Switch setting error

Lit

Lit

Lit

Not lit

Checked when

power is turned

ON.

UNWIRE

system

D and V24

short-circuited.

Lit

Lit

Not lit

Not lit

Checked all the

time.

sys e

error

D and G short-circuited,

or D and G connection

reversed.

Lit

Not lit

Lit

Not lit

e

End Unit error or D line

disconnected

Lit

Not lit

Not lit

Lit

2. Function

A Uniwire Interface Module functions as the master station of a Uniwire System.

3. Specifications

1) Hardware Specifications

The following table shows the hardware specifications of the Uniwire Interface Module.

Table 4.67 Hardware Specifications of Uniwire Interface Module

Items

Specifications

Model Name

UNIWIRE I/F

Model No.

JAMSC-120CRD21110

External Dimensions

Width: 40.3 mm

Height: 130 mm

Depth: 103.9 mm

Approximate Mass

300g

Internal Current Consumption

200 mA

Maximum Heating Value

8.2 W

Hot Swapping (Removal/Inser-

tion Under Power)

Permitted

Mounting Location

Any slot of any Rack.

External Power Supply

The following regulated DC power supply is necessary to oper-

ate the Module.

D

22.8 to 26.4 VDC; ripple: 0.5V

P-P

D

0.2 A (power supply to Uniwire System devices not included.)