System Components: Functions and Specifications
4.4.8 Uniwire Interface Module
— 4-160 —
If an error occurs either in the Module or in the Uniwire System, the READY, ERR1, ERR2 and
ERR3 indicators will operate as follows:
Type
Error
READY
ERR1
ERR2
ERR3
Remarks
Module
error
ROM error
Not lit
Lit
Not lit
Not lit
Checked when
power is turned
error
RAM error
Not lit
Not lit
Lit
Not lit
power is turned
ON.
Internal watchdog timer
error
Not lit
Not lit
Not lit
Lit
Checked all the
time.
Switch setting error
Lit
Lit
Lit
Not lit
Checked when
power is turned
ON.
UNWIRE
system
D and V24
short-circuited.
Lit
Lit
Not lit
Not lit
Checked all the
time.
sys e
error
D and G short-circuited,
or D and G connection
reversed.
Lit
Not lit
Lit
Not lit
e
End Unit error or D line
disconnected
Lit
Not lit
Not lit
Lit
2. Function
A Uniwire Interface Module functions as the master station of a Uniwire System.
3. Specifications
1) Hardware Specifications
The following table shows the hardware specifications of the Uniwire Interface Module.
Table 4.67 Hardware Specifications of Uniwire Interface Module
Items
Specifications
Model Name
UNIWIRE I/F
Model No.
JAMSC-120CRD21110
External Dimensions
Width: 40.3 mm
Height: 130 mm
Depth: 103.9 mm
Approximate Mass
300g
Internal Current Consumption
200 mA
Maximum Heating Value
8.2 W
Hot Swapping (Removal/Inser-
tion Under Power)
Permitted
Mounting Location
Any slot of any Rack.
External Power Supply
The following regulated DC power supply is necessary to oper-
ate the Module.
D
22.8 to 26.4 VDC; ripple: 0.5V
P-P
D
0.2 A (power supply to Uniwire System devices not included.)
4