System Components: Functions and Specifications
4.4.6 MEMOBUS Modules (RS-422)
— 4-136 —
When a status error has occurred, the READY, ERR1, and ERR2 indicators will operate as
shown in the following table:
Type of Error
READY
ERR1
ERR2
Remarks
ROM error
Flashes
Not lit
Not lit
Checked all the time.
RAM error
Not lit
Flashes
Not lit
Checked when power is turned ON.
Common memory error
Flashes
Flashes
Not lit
Checked when power is turned ON.
Watchdog timer error
Not lit
Flashes
Flashes
Checked all the time.
2. Function
1) The MEMOBUS Module (RS-422) is equipped with two MEMOBUS ports for RS-422
communications.
2) The MEMOBUS Module (RS-422) performs communications using RS-422 (master
communications or slave communications) through the MEMOBUS ports. The MEMO-
BUS protocol or any other protocol can be used for the communications protocol.
3) The features of the MEMOBUS Module (RS-422) are as follows:
a) The transmission distance can be extended up to 500 m without a modem.
b) Communications in 1:n format are possible without a modem: 1 master and up to 31
slaves.
4) The MEMOBUS Module (RS-422) can use either 2-line or 4-line communications.
Note
The maximum transmission distance and the number of slaves for 1:n communications vary
according to the specifications of connected communications devices.