Function – Yaskawa MEMOCON GL120 User Manual
Page 223
4.4 Communications Modules
— 4-167 —
If an error occurs either in the Module or in the Uniwire System, the READY, ERR1, ERR2 and
ERR3 indicators will operate as follows:
Type
Error
READY
ERR1
ERR2
ERR3
Remarks
Module ROM error
Not lit
Lit
Not lit
Not lit
Checked when power
i
d ON
error
RAM error
Not lit
Not lit
Lit
Not lit
p
is turned ON.
Internal watchdog timer error
Not lit
Not lit
Not lit
Lit
Checked all the time.
Switch setting error
Lit
Lit
Lit
Not lit
Checked when power
is turned ON.
Unwire
D and V24 short-circuited.
Lit
Lit
Not lit
Not lit
Checked all the time.
system
error
D and G short-circuited, or D and G
connection reversed.
Lit
Not lit
Lit
Not lit
End Unit error or D line disconnected
Lit
Not lit
Not lit
Lit
H-System error
Lit
Lit
Not lit
Lit
2. Function
1) The Uniwire (H) I/F is an interface module compatible with the Uniwire System
manufactured by the NKE Corporation to reduce wiring. The Uniwire (H) I/F has the
following main functions.
• Communications with Uniwire System I/O Terminal Units
• Address detection of I/O Terminal Units with errors (for H-System)
• Notification to the CPU Module of information on I/O Terminal Units for which errors
have been detected (for H-System)
2) Interface Function
The Uniwire (H) I/F can be set for either a Normal System or a H-System. Both Normal
System and H-System I/O Terminal Units are available. Contact the NKE Corporation for
details on I/O Terminal Units.
4