106 — 2. function, Specifications – Yaskawa MEMOCON GL120 User Manual
Page 162
![background image](https://www.manualsdir.com/files/819912/content/doc162.png)
System Components: Functions and Specifications
4.4.2 Remote I/O Driver Module
— 4-106 —
2. Function
Remote I/O Driver Modules function as the master station for a Remote I/O System using
coaxial cable as the transmission cable.
3. Specifications
The specifications of the Remote I/O Driver Module are shown in the following table.
Table 4.44 Specifications of Remote I/O Driver Module
Item
Specifications
Model Name
RIOD-COAX
Model No.
JAMSC-120CRD13100
Internal Current Consumption
800 mA
Maximum Heating Value
4.0 W
Hot Swapping (Removal/Insertion
Under Power)
Not permitted
Approximate Mass
300 g
External Dimensions
Width:
1
40.3 mm
Height: 130 mm
Depth: 103.9 mm
Remote I/O Port Specifications
Topology
(Communications
Network)
Bus
Media Access Control
Method
Multi-drop (1:n communications)
Media
(Transmission Medium)
Coaxial cable (75Ω)
Modulation Method
Base band
Encoding Method
Manchester code
Baud Rate
Choose from 0.5/1/2/4 Mbps
Transmission Distance
Transmission distance varies according to the baud rate
and specifications of coaxial cable. If, for example, the
baud rate is 4 Mbps and 12C-5AF Coaxial Cable is
used, it is possible to transmit up to 1 km max.
Number of Stations
15 max. (Up to 15 Remote I/O Receiver Modules are
connectable.)
Error Measures (RAS)
Automatic parallel off and malfunctioning station
recovery
Synchronization Method
Frame
Communications Format
Conforms to HDLC.
Insulation Method
Pulse transformer
Connector
BNC connector
4