189 — 2. function, Specifications – Yaskawa MEMOCON GL120 User Manual
Page 245
4.4 Communications Modules
— 4-189 —
2. Function
The YENET 1600-D Module functions as station of a YENET 1600-D System.
3. Specifications
1) Module Specifications
Table 4.77 Specifications of YENET 1600-D Module
Item
Specifications
Name
YENET 1600-D Module
Model Name
YENET 1600-D
Model No.
JAMSC-120NDN31110
External dimensions
Width: 40.3 mm
Height: 130 mm
Depth: 103.9 mm
Approximate Mass
300 g
Internal Current Consumption
250 mA
Maximum Heating Value
1.9 W
Hot Swapping
(Removal/Insertion Under
Power)
Permitted
External Power Supply Voltage
For communication: 24 VDC, 25 mA
External Connections
Removable terminal block for field connections (5-pin with flange,
made by Phoenix Contact Co, model number MSTB2.5/5-STF-5.08)
Mounting Location
Any slot of any Rack
Communications
Port
S
Connection
Method
Multi-drop, T-branch (1:N)
o
Specifications
Baud Rate
500, 250, or 125 Kbps (selectable)
Transmission
Medium
Special 5-wire cable (2 signal lines, 2 power lines, 1 shield), or 3-wire
cable (separate power cable required)
Transmission
Distance
Baud Rate
Network Length
(Max.)
Drop Line
Length (Max.)
Total Drop Line
Length (Max.)
s a ce
500 Kbps
100 m
6 m
39 m
250 Kbps
250 m
6 m
78 m
125 Kbps
500 m
6 m
156 m
Node
Address
0 to 15
Number of
Units
Connected
63 max.
Status
Information
Can be monitored in Monitor Mode
Transmission
Error
Detection
CRC errors, duplicate node address check
2) I/O Specification
The YENET 1600-D Module operates in Master Mode or Slave Mode according to set-
tings made from the MEMOSOFT.
4