3 specifications of power supply modules – Yaskawa MEMOCON GL120 User Manual
Page 66
System Components: Functions and Specifications
4.2.3 Specifications of Power Supply Modules
— 4-10 —
4.2.3 Specifications of Power Supply Modules
1. Specifications of PS10 (Model No. JRMSP-120CPS11300)
PS10 specifications are shown in the following table.
Table 4.3 Specifications of PS10
Item
Specifications
Input
Rated Voltage
100/200 VAC (Selectable)
p
Permissible Voltage Range
85 to 132 VAC or 170 to 264 VAC
Rated Frequency
50/60 Hz
Permissible Frequency
Range
47 to 63 Hz
Permissible Momentary Pow-
er Interruption Time
Less than one cycle. Momentary power interrup-
tion intervals must be 1 s min.
Wave Distortion Factor
10% or less
Power Consumption
1) At 100 VAC: 100 VA max.
2) At 200 VAC: 120 VA max.
Current Leakage
1) At 132 VAC: 1.4 mA max.
2) At 264 VAC: 2.8 mA max.
Inrush Current
1) At 132 VAC, cold start: 25 A max.
2) At 264 VAC, cold start: 50 A max.
No. of Phases
Single-phase
Output Char-
i i
Rated Voltage
5.1 VDC
p
acteristics
Rated Current
7.0 A
Fuse
Standard fusing glass tube fuse (250 VAC, 3.15 A)
Field Wiring Terminals
1) Equipped with three types of terminals: field
wiring terminals (AC1, AC2), filter ground
terminal (ACG), and protective ground terminal
(FG).
2) M4 Phillips screws are used for the terminals.
3) Use wire size 1.5 mm
2
(AWG16) to 2.5 mm
2
(AWG13) to connect to the terminals.
Hot Swapping
(Removal/Insertion Under Power)
Not permitted.
Maximum Heating Value
20 W
Approximate Mass
600 g
External Dimensions
Width:
1
81 mm
Height:
130 mm
Depth:
103.9 mm
4