beautypg.com

Yaskawa MEMOCON GL120 User Manual

Page 94

background image

System Components: Functions and Specifications

4.3.3 Specifications of CPU Modules cont.

— 4-38 —

Item

Specifications

Program Memory Capacity

16K words (1 word: 24 bits)

Maximum I/O Points/Registers

1) Digital I/O points: 1,024 points max. (1 point: 1 bit)

2) I/O registers: 512 registers max. (1 register: 16 bits)

3) Local I/O:

D

Number of channels: 1

D

Number of Racks: 4 Racks max. including CPU Rack.

D

Number of mountable I/O Modules: 54 max.
The total number of points/registers including all remote input/output points must
meet the above conditions 1) and 2).

4) Remote I/O:

D

Number of channels: 2

D

Number of stations per channel: 15

D

Number of Racks per channel: 4 Racks max.

D

Number of I/O points per station:
(Digital input points ÷ 8) + (Input registers x 2) ≤ 512 bytes

(Digital output points ÷ 8) + (Output registers x 2) ≤ 512 bytes

The total number of points/registers including all remote input/output points must
meet the above conditions 1 and 2.

Maximum Number of Coils and

Relays

1) When the number of data registers is the initial value, the following condition must

be met:
(Number of coils) + (Number of relays) ≤ 65,520

2) The maximum value of each reference can be freely set within the above limit from

the Programming Panel (Unit: point (1 point = 1 bit)).

Coil/Relay

Setting range

Setting unit

Defaults

Example 1

Example 2

Coils

16 to 65,472

16

8,192

60,400

65,472

Link coils

0 to

6

4,096

1,024

2,048

2,048

0

MC coils

0 to

65,

512

256

512

512

0

MC control

coils

0 to

65,

320

160

320

320

0

Input relays

16 to 65,472

16

1,024

1,024

16

MC relays

0 to

65,

512

256

512

512

0

MC control

relays

0 to

65,

512

256

512

512

0

M code

relays

0 to

65,

192

96

192

192

0

Note: Number of I/O allocatable input relays = 1024 − (Number of output coils which

have been allocated)