Yaskawa MEMOCON GL120 User Manual
Page 256
![background image](https://www.manualsdir.com/files/819912/content/doc256.png)
System Components: Functions and Specifications
4.4.13 Ethernet Interface Module
— 4-200 —
If an error occurs, the READY indicator will go OFF and the ERROR indicator will light
or flash as described in the following table.
Type of
Error
ERROR Indicator Status
ROM error
The ERROR indicator will flash one time, go OFF for 1 s, and
then repeat the cycle.
RAM error
The ERROR indicator will flash two times, go OFF for 1 s, and
then repeat the cycle.
DPM error
The ERROR indicator will flash six times, go OFF for 1 s, and
then repeat the cycle.
Watchdog
timer error
The ERROR indicator will flash seven times, go OFF for 1 s, and
then repeat the cycle.
Other error
The ERROR indicator will flash eight times, go OFF for 1 s, and
then repeat the cycle.
2. Function
The Ethernet Interface Module functions as an interface for connecting to GL120 and
GL130 Ethernet Network Systems.
4