System Components: Functions and Specifications
4.4.7 PC Link Module
— 4-148 —
When a status error has occurred, the READY, PP ERR, and L-ERR indicators will operate as
shown in the following table:
Type of Error
READY
PP ERR
L-ERR
Remarks
ROM error
Flashes
Flashes
Flashes
Checked all the time.
RAM error
Flashes
Not lit
Flashes
Checked when power is turned ON.
Common memory error
Flashes
Flashes
Not lit
Checked when power is turned ON.
Watchdog timer error
Lit
Flashes
Flashes
Checked all the time.
Station address error
Lit
Flashes
Not lit
Checked when power is turned ON.
2. Function
The PC Link Module functions as station of a PC Link System using coaxial cable for the
transmission cable.
3. Specifications
The specifications of the PC Link Module are shown in the following table.
Table 4.62 Specification of PC Link Module
Item
Specifications
Model Name
PCLINK-COAX
Model No.
JAMSC-120NFB23100
External Dimensions
Width: 40.3 mm
Height: 130 mm
Depth: 103.9 mm
Approximate Mass
300 g
Internal Current Consumption
800 mA
Maximum Heating Value
4.0 W
Hot Swapping (Removal/Insertion
Under Power)
Permitted
4