Yaskawa MEMOCON GL120 User Manual
Page 448
!
!
Low Voltage Directives
6.1.4 Using Power Supply Modules cont.
— 6-10 —
H. Filter Ground Terminal (ACG)
The filter ground terminal is used to ground the input line filter built inside Power Supply
Module. This terminal is short-circuited with functional earth terminal when the Power
Supply Module is shipped.
Caution
Make sure not to remove the short piece from between the filter ground terminal (ACG) and
the functional earth terminal (FE).
I. Built-in Fuse
1) The fuse inside a Power Supply Module is to prevent the Power Supply Module from
damage which may occur in the following causes:
a) External causes: For example, when an over-voltage is applied to the field wiring ter-
minals of Power Supply Module.
b) Internal causes: For example, when foreign matter such as chips happen to be pres-
ent inside a Power Supply Module, thereby short-circuiting internal
circuits.
2) When the built-in fuse burns out, the “POWER” indicator of Power Supply Module will go
out. If the fuse burns out, eliminate the cause of fuse breakage and replace it with a spare
Power Supply Module.
Caution
Do not replace the built-in fuses of the Power Supply Modules.
If the built-in fuses are replaced by anyone other than a Yaskawa-approved technician, a
failure or malfunction may occur in the Power Supply Modules.
6