Yaskawa MEMOCON GL120 User Manual
Page 84
System Components: Functions and Specifications
4.3.1 Appearance of CPU Modules cont.
— 4-28 —
4. Appearance of CPU21 (Model No. DDSCR-120CPU34110)
Built-in battery
DIP switch
Key switch
Rotary switch 1
MEMOBUS port
MEMOBUS PLUS port
Module description
(120CPU34110)
Color code (yellow)
LED area
Module mounting screw
(Use M4 Phillips screwdriver.)
Rotary switch 2
PC Card slot
LED
Color
Indication when ON
READY
Green
CPU Module is normal.
RUN
Green
CPU Module is running.
MB+/ERR
Green
MEMOBUS PLUS port is transmitting/receiving data
normally.
Red
Transmitting/receiving error has occurred in
MEMOBUS PLUS port.
CRD/BAT
Green
Lit:
CPU Module is accessing PC Card.
Flash: PC Card error has occurred in CPU Module.
Red
Voltage in the built-in battery in CPU Module is running
down.
ACTIVE
Green
Access to CPU Module from other Module is possible.
TX/ERR
Green
MEMOBUS port is transmitting data normally.
/
Red
Transmitting/receiving error has occurred in
MEMOBUS port.
RX
Green
MEMOBUS port is receiving data normally.
MEM PRT
Green
Key switch has selected memory protect ON.
Figure 4.11 Appearance of CPU21
Note
Make sure to replace the battery in the CPU Module within two weeks after the CRD/BAT
indicator lights red (replacement battery: BR-2/3A-1).
Programs or data stored in the CPU Module or Motion Modules will be lost if replacement is
delayed.
4
RUN
READY
120 CPU 341 10
MB+/ERR
CRD/BAT
ACTIVE
TX/ERR
RX
MEM PRT
LED area