5.1 Designing the Control Panel

— 5-13 —

2) When the Modules shown in Table 5.4 are installed in a control panel, the depth of the

control panel necessary to mount a Module (dimension D) is as follows:

a) D for a Mounting Base mounted to a device mounting steel plate (dimension D1):

Dimension D1 = (depth of the Module) + (cable connection length) + 17 mm
Refer to Table 5.4 and Example 3.

b) D for Mounting Base mounted to a DIN track (Dimension D2):

Dimension D2 = (depth of the Module) + (cable connection length) + 17 + 6 mm
Refer to Table 5.4 and Example 4.