beautypg.com

Yaskawa MEMOCON GL120 User Manual

Page 184

background image

System Components: Functions and Specifications

4.4.5 MEMOBUS Modules (RS-232)

— 4-128 —

When a status error has occurred, the READY, ERR1, and ERR2 indicators will operate as
shown in the following table:

Type of Error

READY

ERR1

ERR2

Remarks

ROM error

Flashes

Not lit

Not lit

Checked all the time.

RAM error

Not lit

Flashes

Not lit

Checked when power is turned ON.

Common memory error

Flashes

Flashes

Not lit

Checked when power is turned ON.

Watchdog timer error

Not lit

Flashes

Flashes

Checked all the time.

2. Function

1) The MEMOBUS Module (RS-232) is equipped with two MEMOBUS ports (master/slave)

for RS-232C communications.

2) The MEMOBUS Module (RS-232) runs communications using RS-232C (master com-

munications or slave communications) through MEMOBUS ports. MEMOBUS protocol
or any other protocol can be used for the communications protocol.

3. Specifications

The specifications of MEMOBUS Module (RS-232) are shown in the following table.

Table 4.54 Specifications of MEMOBUS Module (RS-232)

Item

Specification

Model Name

MEMOBUS-RS232

Model No.

JAMSC-120NOM26100

External Dimensions

Width:

1

40.3 mm

Height: 130 mm

Depth: 103.9 mm

Approximate Mass

300 g

Internal Current Consumption

600 mA

Maximum Heating Value

3.0 W

Hot Swapping (Removal/Insertion

Under Power)

Permitted

4

This manual is related to the following products: