beautypg.com

225 — 2. analog input modules – Yaskawa MEMOCON GL120 User Manual

Page 281

background image

4.5 I/O Modules

— 4-225 —

2. Analog Input Modules

1) Function

An Analog Input Module converts the analog signals coming from weight sensors, tem-
perature sensors, etc., into numeric data appropriate for PLC internal processing. The
converted numeric data is stored by the CPU Module as the input registers in state
memory.

2) Specifications

The following table shows the main specifications of the Analog Input Modules.

Table 4.92 Main Specifications of Analog Input Modules

Name

Model

Name

Model

No.

Input

Signal

Range

Overall

Accura-

cy

Resolution

and Data

Types

Input Im-

pedance

Number

of

Chan-

nels

Internal

Current

Con-

sumption

Maxi-

mum

Heat-

ing

Value

Hot

Swap-

ping

Analog

Input

Module

(±10 V,

4 chan-

l )

A/D-

VOL-4CH

JAMSC-

120AVI0

2000

−10 to

+10 V

±0.5%

F.S.

(25°C)

0 to 4000

mode: 12

bits, binary

between 0

and 4000

1 MΩ min. 4

450 mA

2.3 W

Per-

mitted

nels)

±1.0%

F.S. (0

to 60°C)

± 2000

mode: 12

bits, 2’s

complement

between

−2000 and

+2000

Analog

Input

Module

(0 to 10

V,

4 chan-

nels)

A/D

0−10V

4CH

JAMSC-

120AVI0

2100

0 to

+10 V

±0.5%

F.S.

(25°C)
±1.0%

F.S. (0

to 60°C)

12 bits,

binary be-

tween 0 and

4000

1 MΩ min. 4

450 mA

2.3 W

Per-

mitted

Analog

Input

Module

(4 to 20

mA,

4 chan-

nels)

A/D-

CUR-4CH

JAMSC-

120ACI

02000

Current

input: 4

to 20

mA
Voltage

input:

1 to 5 V

±0.5%

F.S. (25
°C)
±1.0%

F.S. (0

to 60°C)

12 bits,

binary be-

tween 0 and

4000

Current

input: 250

voltage in-

put:

1 MΩ min.

4

450 mA

2.3 W

Per-

mitted

Other specifications

1) Slots required: 1

2) Approx. mass: 300 g

3) Width: 40.3 mm

Height: 130 mm

Depth: 103.9 mm

4) Field connections: Terminal block

4