14-19
IM 04L31A01-01E
Specifications
14
Isolation
Insulation resistance:
Between each terminal and earth: 20 MΩ or more (at 500 VDC)
Withstand voltage:
Between the power terminal and earth:
1500 VAC at 50/60 Hz for one minute
Between the contact output terminal and earth:
1500 VAC at 50/60 Hz for one minute
Between the measurement input terminal and earth:
1500 VAC at 50/60 Hz for one minute
Mutually between measurement input terminals:
1000 VAC at 50/60 Hz for one minute
Between the contact input terminal and earth:
500 VDC for one minute
Between the current output terminal and earth:
500 VAC at 50/60 Hz for one minute
Between the voltage pulse output terminal and earth:
500 VAC at 50/60 Hz for one minute
Between the transistor contact output and earth:
500 VDC for one minute
Grounding resistance:
100 Ω or less
Standard Performance
Measurement accuracy: The following specifications apply to operation of the CX2000
under standard operation conditions:
Temperature:
23 ± 2 °C
Humidity:
55% ± 10% RH
Supply voltage: 90 to 132 or 180 to 250 VAC
Power frequency: 50/60 Hz ± 1% Warm-up time: At least 30 minutes.
Other ambient conditions such as vibration should not
adversely affect the operation of the CX2000.
Input Type
DCV
TC
(Excluding the
reference
junction
compensation
accuracy)
RTD
Measurement Accuracy (Digital Display)
±(0.1% of rdg + 2digits)
±(0.1% of rdg + 3digits)
±(0.15% of rdg + 1°C)
Except R, S: 0 to 100°C: ±3.7°C,
100.0 to 300°C: ±1.5B: 400 to 600°C: ±2°C,
Accuracy at less than 400°C is not warranted.
±(0.15% of rdg + 0.7°C)
Except ±(0.15% of rdg + 1°C) at –200 to –100°C
±(0.15% of rdg + 0.5°C)
±(0.15% of rdg + 0.5°C)
Except ±(0.15% of rdg + 0.7°C) at –200 to –100°C
±(0.15% of rdg + 0.7°C)
±(0.15% of rdg + 1°C)
±(0.15%of rdg + 0.5°C)
Except ±(0.15% of rdg + 0.7°C at –200 to 100°C)
±(0.25% of rdg ± 2.3°C)
0 to 450°C Accuracy
not
guanteed
450 to 750°C ±(0.9% of rdg + 16.0°C)
750 to 1100°C ±(0.9% of rdg + 6.0°C)
1100 to 1900°C ±(0.9% of rdg + 2.0°C)
±(0.3% of rdg ± 2.8°C)
±(0.15% of rdg + 0.3°C)
Max.Resolution of Digital Display
10 µV
10 µV
100 µV
1mV
10mV
10mV
0.1°C
Range
20 mV
60 mV
200 mV
2 V
6 V
20 V
50 V
R
S
B
K
E
J
T
N
W
L
U
PLATINEL
PR40-20
W3Re/W25Re
Pt100
JPt100
1mV
Measurement accuracy during scaling:
Accuracy during scaling (digits) = measurement accuracy
(digits) × multiplier + 2 digits (rounded up)
* Fractions rounded up
Reference junction compensation:
INT (internal) and EXT (external) switchable (common to all
channels)
14.8 General Specifications