Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 172
4-12
IM 04L31A01-01E
Setup Items
Setting Parameters Related to Output Processing
• Loop number
Setup items of [Control output], [Cycle time] and [Analog-output type] are set for each
loop. When changing these parameters, this setting is used to select the target loop
number [1] to [6] (initial value is 1). The loop number is displayed up to the number of
loops you specified at the time of purchase.
Note
The following item boxes do not appear, if the [Control mode] box under [Control] > [#1
Control action, Input setting] is set to [Cascade].
• Control output
Select the type of control output from the following.
• Relay
• Voltage-pulse
• Current-output
• On/Off-control
• Cycle time
Set the cycle time (control output cycle) for the time proportional PID in the range of
[1] s to [1000] s. This setting is valid only when [Control output] is set to [Relay] or
[Voltage-pulse].
• Analog-output type
Select the type of output current during current output from below. This setting is valid
only when [Control output] is set to [Current-output].
4-20mA, 0-20mA, 20-4mA, and 20-0mA
4.3 Control > Output processing