9 program pattern settings > event output settings, Event output settings -12, 9 event output settings – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 221
![background image](/manuals/360271/221/background.png)
5-12
IM 04L31A01-01E
5.9
Event Output Settings
This section explains the setting procedure for event output during program control and
program pattern end signaling.
Procedure
Opening the Setting Display
Press the keys in the following sequence:
MENU key
(switch to setting mode(control)) >
#7 soft key
(select [Program-control
parameters] >
#2 soft key
(select [Event output setting])
The following display appears.
Setup Procedure
1.
Use the
arrow keys
to move the cursor (blue) to the item box you wish to
change.
A soft key menu is displayed at the bottom of the display.
2.
Press the
soft key
corresponding to the value you wish to select.
The box for the item you changed turns yellow, and the cursor moves to the next
item box.
3.
Repeat steps 1 and 2 to change the value of all the items you wish to change.
4.
Press the
DISP/ENTER key
to confirm the changes.
The boxes for the items you changed turn from yellow to white, and the cursor
returns to the first item box.