Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 197
![background image](/manuals/360271/197/background.png)
4-37
IM 04L31A01-01E
Control Function Related Setup Operations
4
Note
•
This instrument has several functions for outputting contact signals from DO. If output
from multiple functions occurs for the same DO, the following priorities apply.
FAIL/self diagnosis output > DIO operation monitoring function > other (alarm output etc.)
•
For the energized/de-energized status of the DO set as the destination of the DIO
operation monitoring function, follow the procedure in section 4.4, "Control > Relay."
•
For the hold/nonhold status of the DO set as the destination of DIO operation monitoring
function, follow the procedure in section 4.4, "Control > Relay."
• DI Number
Sets the DI number displayed on the CX screen. This is not displayed if DO-1, DO-2,
or DO-2P was selected for the DIO type.
• Tag and Tag Comment
Enter a tag and tag comment of the DIO operation monitoring function using 8
characters or less.
• Operation Status Display
Set the color and label used when displaying the DO status on the CX screen. You
can enter settings for both ON and OFF statuses.
4.14 DIO Operation Monitoring Function Settings (Style Number S3 or Later)