Chapter 14 specifications, 1 input section specifications, Input section specifications -1 – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 349: Common to control and measurement, Control input
14-1
IM 04L31A01-01E
Specifications
14
Chapter 14 Specifications
14.1 Input Section Specifications
Common to Control and Measurement
Thermocouple burnout:
Detection ON/OFF switchable (on each channel)
Burnout up scale/down scale switchable
A/D integral time:
Select from 20 ms (50 Hz), 16.7 ms (60 Hz), 100 ms (50/60
Hz), and AUTO (automatically switches between 20 ms and
16.7 ms from the power supply frequency)
Control Input
Number of inputs:
Up to 10 inputs (depends on the model and control mode)
Period:
250, 500, 1000 ms (synchronized with the control period, 1000
ms when the A/D integral time is set to 100 ms)
Input type:
DCV (DC voltage), TC (thermocouple), RTD (resistance
temperature detector), DCA (DC current, by adding an external
shunt resistor)
Linear scaling:
Input ranges capable of scaling: TC, RTD, DCA
Available range of scaling: –30000 to 30000 and the span within 30000
Decimal point position:
Can be set arbitrarily
Unit:
Can be set arbitrarily using up to 6 characters
Standard signal burnout: For control input, burnout detection is possible not only on
thermocouples but also standard signals.
PV input computation:
Input processing, square root computation (low cut 0.0 to 5.0%), ten-
segment linearizer approximation, ten-segment linearizer bias, bias
addition (in the measurement span of –100.0 to 100.0%), first-order
lag computation (time constant from 1 to 120 s, off)
Auxiliary input computation: Input processing, square root computation (low cut 0.0 to
5.0%), bias addition (in the measurement span of –100.0 to
100.0%), ratio computation (0.001 to 9.999), first-order lag
computation (time constant from 1 to 120 s, off)
Input Range and Measurable Range:
Range
20mV
60mV
200mV
2V
6V
20V
50V
R
*1
S
*1
B
*1
K
*1
E
*1
J
*1
T
*1
N
*1
W
*2
L
*3
U
*3
PLATINEL
PR40-20
W3Re/W25Re
Pt100
*4
JPt100
*4
1 to 5V
Measurable Range
–20.00 to 20.00mV
–60.00 to 60.00mV
–200.0 to 200.0mV
–2.000 to 2.000V
–6.000 to 6.000V
–20.00 to 20.00V
–50.00 to 50.00V
0.0 to 1760.0°C
0.0 to 1760.0°C
0.0 to 1820.0°C
–200.0 to 1370.0°C
–200.0 to 800.0°C
–200.0 to 1100.0°C
–200.0 to 400.0°C
0.0 to 1300.0°C
0.0 to 2315.0°C
–200.0 to 900.0°C
–200.0 to 400.0°C
0.0 to 1400.0°C
0.0 to 1900.0°C
0.0 to 2400.0°C
–200.0 to 600.0°C
–200.0 to 550.0°C
1.000 to 5.000V
DCV
Only linear
scaling allowed
TC
RTD
*5
Standard signal
*1
:
R, S, B, K, E, J, T, N: IEC584-1(1995), DIN IEC584, JIS C1602-1995
*2
:
W: W-5% Re/W-26% Re(Hoskins Mfg. Co.), ASTM E988
*3
:
L: Fe-CuNi, DIN43710, U: Cu-CuNi, DIN43710
*4
:
Pt100: JIS C1604-1997, IEC751-1995, DIN IEC751-1996
JPt100: JIS C1604-1989, JIS C1606-1989
*5
:
Measuring current: i = 1mA
Input