14.1 Input Section Specifications

Common to Control and Measurement

Thermocouple burnout:

Detection ON/OFF switchable (on each channel)
Burnout up scale/down scale switchable

A/D integral time:

Select from 20 ms (50 Hz), 16.7 ms (60 Hz), 100 ms (50/60
Hz), and AUTO (automatically switches between 20 ms and
16.7 ms from the power supply frequency)

Control Input

Number of inputs:

Up to 10 inputs (depends on the model and control mode)

Period:

250, 500, 1000 ms (synchronized with the control period, 1000
ms when the A/D integral time is set to 100 ms)

Input type:

DCV (DC voltage), TC (thermocouple), RTD (resistance
temperature detector), DCA (DC current, by adding an external
shunt resistor)

Linear scaling:

Input ranges capable of scaling: TC, RTD, DCA

Available range of scaling: –30000 to 30000 and the span within 30000
Decimal point position:

Can be set arbitrarily

Unit:

Can be set arbitrarily using up to 6 characters

Standard signal burnout: For control input, burnout detection is possible not only on

thermocouples but also standard signals.

PV input computation:

Input processing, square root computation (low cut 0.0 to 5.0%), ten-
segment linearizer approximation, ten-segment linearizer bias, bias
addition (in the measurement span of –100.0 to 100.0%), first-order
lag computation (time constant from 1 to 120 s, off)

Auxiliary input computation: Input processing, square root computation (low cut 0.0 to

5.0%), bias addition (in the measurement span of –100.0 to
100.0%), ratio computation (0.001 to 9.999), first-order lag
computation (time constant from 1 to 120 s, off)

Input Range and Measurable Range:

Range

20mV
60mV

200mV

2V
6V

20V
50V

R

*1

S

*1

B

*1

K

*1

E

*1

J

*1

T

*1

N

*1

W

*2

L

*3

U

*3

PLATINEL

PR40-20

W3Re/W25Re

Pt100

*4

JPt100

*4

1 to 5V

Measurable Range

–20.00 to 20.00mV
–60.00 to 60.00mV
–200.0 to 200.0mV

–2.000 to 2.000V
–6.000 to 6.000V
–20.00 to 20.00V
–50.00 to 50.00V

0.0 to 1760.0°C
0.0 to 1760.0°C
0.0 to 1820.0°C

–200.0 to 1370.0°C

–200.0 to 800.0°C

–200.0 to 1100.0°C

–200.0 to 400.0°C

0.0 to 1300.0°C
0.0 to 2315.0°C

–200.0 to 900.0°C
–200.0 to 400.0°C

0.0 to 1400.0°C
0.0 to 1900.0°C
0.0 to 2400.0°C

–200.0 to 600.0°C
–200.0 to 550.0°C

1.000 to 5.000V

DCV
Only linear
scaling allowed

TC

RTD

*5

Standard signal

*1

:

R, S, B, K, E, J, T, N: IEC584-1(1995), DIN IEC584, JIS C1602-1995

*2

:

W: W-5% Re/W-26% Re(Hoskins Mfg. Co.), ASTM E988

*3

:

L: Fe-CuNi, DIN43710, U: Cu-CuNi, DIN43710

*4

:

Pt100: JIS C1604-1997, IEC751-1995, DIN IEC751-1996

JPt100: JIS C1604-1989, JIS C1606-1989

*5

:

Measuring current: i = 1mA

Input