1 settings related to measurement inputs, Settings related to measurement inputs -1 – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 247
7-1
IM 04L31A01-01E
Measurement Function Related Setup Operations
7
Chapter 7 Measurement Function Related Setup Operations
7.1
Settings Related to Measurement Inputs
This section explains how to set parameters related to measurement input of the
measurement function such as A/D integral time, scan interval, and range.
Procedure
Opening the Setting Display
• When Setting the A/D Integral Time, Scan Interval, Etc.
Burn out and RJC settings cannnot be entered on 0 measurement channel models
(the setting menu is not displayed).
Press the keys in the following sequence:
MENU key
(switch to the Setting mode (Control)) >
Hold down the FUNC key for
3 seconds
(switch to basic setting mode) >
#1 soft key
(select [Alarm, A/D,
Temperature])
The following display appears.
• When Setting the Range
Range settings cannnot be entered on 0 measurement channel models. An error
message will appear if the range or alarm setting screen is selected.
Press the keys in the following sequence:
MENU key
(switch to the Setting mode (Control)) >
MENU key
(switch to the Set
mode) >
#1 soft key
(select [Range, Alarm])
The following display appears.