Code
Message
280
IP address is not set or FTP function is not available.
Further details are provided by the character string that appears after error code 280.
Character String and Details
HOSTADDR
The IP address of the CX2000 has not been specified.
Check the IP address.
*1
DORMANT
Internal processing error.
*2
LINK
Data link is disconnected.
Check the cable connection.
281
FTP mail box operation error.
Further details are provided by the character string that appears after error code 281.
Character String and Details
Internal processing error.
*2
STATUS
Internal processing error.
*2
TIMEOUT
Internal processing error.
*2
PRIORITY
Internal processing error.
*2
NVRAM
Internal processing error.
*2
282
FTP control connection error.
Further details are provided by the character string that appears after error code 282.
Character String and Details
HOSTNAME
Failed the DNS lookup (search the IP address corresponding to the host name).
Check the DNS setting and the destination host name.
*1
TCPIP
Internal processing error.
*2
UNREACH
Failed to connect to a control connection server.
Check the address setting and that the server is running.
OOBINLINE
Internal processing error.
*2
NAME
Internal processing error.
*2
CTRL
The control connection does not exist.
Check that the server does not drop the connection and that it responds within the proper time period.
IAC
Failed to respond in the TELNET sequence.
Check that the server does not drop the connection and that it responds within the proper time period.
ECHO
Failed to transmit data on the control connection.
Check that the server does not drop the connection and that it responds within the proper time period.
REPLY
Failed to receive data on the control connection.
Check that the server does not drop the connection and that it responds within the proper time period.
SERVER
The server is not in a condition to provide the service.
Check that the server is in a condition in which service can be provided.