14-10
IM 04L31A01-01E
Display data file only
Event data file only
Number of control loops: 10 loops, measurement channels: 10 channels
computation channel: 0 channels
Display update
rate (min/div)
Save interval (s)
Sample length
1 min
2 s
Approx. 4 h
5 min
10 s
Approx. 20 h
20 min
40 s
Approx. 3 days
30 min
60 s
Approx. 5 days
60 min
120 s
Approx. 10 days
240 min
480 s
Approx. 40 days
Save interval
Sample length
1 s
Approx. 4 h
5 s
Approx. 20 h
30 s
Approx. 5 days
120 s
Approx. 20 days
Event data file only
Display update
rate (min/div)
Save interval (s)
Sample length
1 min
2 s
Approx. 3 h
5 min
10 s
Approx. 15 h
20 min
40 s
Approx. 2 days
30 min
60 s
Approx. 3 days
60 min
120 s
Approx. 7 days
240 min
480 s
Approx. 30 days
Display data file
Display data file + event data file
Save interval
Sample length
1 s
Approx. 1 h
5 s
Approx. 5 h
30 s
Approx. 29 h
120 s
Approx. 5 days
Manual sampled data:
Trigger: Key operation, communication command, or remote input
Data format: ASCII
Maximum number of data sets that the internal memory can hold: 50
TLOG data (only on models with the computation function):
Trigger: Timeout of the timer
Data format: Binary
Maximum number of data sets that the internal memory can
hold: 400 (or within 16 files)
Report data (only on models with the computation function):
Type: Hourly, daily, hourly + daily, daily + weekly, daily + monthly
Data format: ASCII
Maximum number of data sets that the internal memory can hold: 40
Trigger function:
Event data file: Select the mode from FREE, TRIG, and ROTATE
Display data file + event data file: Select the mode from TRIG
and ROTATE
Display copy function:
Copy method: Key operation, communication command, or
remote input
Data format: PNG
Destination:
External storage medium or communication output
14.5 Storage Function