Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 268
8-11
IM 04L31A01-01E
Operations for Changing the Displayed Contents
8
8.8
Measurement Function > Changing the Display
Update Rate of the Trend Display
This section explains how to change the display update rate of the trend display.
Procedure
Setup Display
Press the keys in the following sequence:
MENU key
(switch to Set mode) >
#3 soft key
(select [Trend/Save
interval,Message,File,User key,DST])
The following display appears.
Setup Procedure
1. Use the
arrow keys
to move the cursor (blue) to [Time/div].
A soft key menu is displayed at the bottom of the display.
2. Press the
soft key
corresponding to the value you wish to select.
The box for the item you changed turns yellow, and the cursor moves to the next
item.
3. Press the
DISP/ENTER key
to confirm the changes.
The boxes for the items you changed turn from yellow to white, and the cursor
returns to the first item.
Setup Items
Setting the Display Update Rate
• Time/div
Select the time corresponding to 1 division of the time axis during trend display from
the following.
1 min, 2 min, 5 min, 10 min, 20 min, 30 min, 1 h, 2 h, 4 h, and 10 h