Control operation error messages – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 340
12-9
IM 04L31A01-01E
12
Troubleshooting
Code
Message
Reference
611
There is no user who can enter to the SETUP mode.
See section 11.3.
620
You must exit setup mode in order for the communications settings to take effect.
Control Operation Error Messages
Code
Message
Explanation/Countermeasures/Ref. section
700
Specified loop number cannot be selected
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
701
Manual mode cannot be selected.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
702
Cascade mode cannot be selected.
Operation error (section 6.1), Contact input error
(section 4.2), communication error (see the
Communication Interface User’s Manual)
703
Stop mode cannot be selected.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
704
Run mode cannot be selected.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
705
Remote mode cannot be selected.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
706
There is no specified target setpoint number.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
710
Auto-tuning cannot be activated.
Operation error (section 6.1), Contact input error
(section 4.2), communication error (see the
Communication Interface User’s Manual)
711
Auto-tuning is activated already.
Operation error (section 6.1), Contact input error
(section 4.2), communication error (see the
Communication Interface User’s Manual)
712
Incorrect PID group number.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
714
Program mode cannot be selected.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
715
There is no specified pattern number.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
716
Pattern number cannot be changed when program operation
Contact input error (section 4.2), communication error
is activated.
(see the Communication Interface User’s Manual)
717
There are no loops with program operation.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
718
Program operation has started already.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
719
Program operation cannot be started.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
720
A disabled start segment number is selected.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
721
Program operation cannot be started when auto-tuning is activated. Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
722
Program operation cannot be started with PV.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
723
Program operation is not activated.
Contact input error (section 4.2), communication error
(see the Communication Interface User’s Manual)
724
Can not operate in the present situation.
Operation error (section 6.1), Contact input error
(section 4.2), communication error (see the
Communication Interface User’s Manual)
725
Modbus Communication Error.
See the Communication Interface User’s Manual.
726
The specified target is not assigned to the control group.
Specify another loop.
729
Can not operation before the starting time of program pattern.
12.1 Messages