Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 23
1-11
IM 04L31A01-01E
Explanation of Functions
3
2
1
4
5
6
7
8
9
10
11
12
13
14
Flow of Setup Procedure
Below is a standard flow of setup procedure in executing control for the first time using
auto operation.
Basic settings
Power ON
PID control
ON/OFF control
Set SP
Adjust control
Operating condition
PID control or
ON/OFF control?
*
Start actual operation
Set PID parameters
Set SP
Start a test run
→ Section 1.6
→ Section 1.7
Set relay hysteresis
• Auto
tuning
• Manual tuning → Section 1.12
• Control output suppression → Section 1.8
• Other
adjustments
(Parameters that cannot be changed
during operation → section 6.1)
→ Section 1.3
Basic settings
Contact input/output
related settings
Basic control settings
Set alarm-related
parameters
→ Section 1.4
→ Section 1.5
Basic settings include the following
parameters.
Set other control
parameters
PV input related settings
→ Section 1.10
*
Set in
"Control Output Type"
of basic control settings
Set alarm-related
parameters
Section 1.9
When using program control, set the items that include “Program control: On” in “Basic
control settings” indicated above. Then, carry out the following settings in addition to
“Target setpoint/PID parameter settings.”
Settings for program control
Pattern initial setting
Wait action setting
Pattern start setting
Program pattern setting
Event setting
Event output setting
Repeat action setting
Pattern initial setting:
Set the pattern numbers, pattern off/on, number of
segments used, segment assignment method, edit
segment number, and Loop number.
Pattern start setting:
Set starting target setpoint and start code (operation
start condition).
Program pattern setting:
Set segment numbers, ramp/soak, final target setpoint,
segment time, ramp-rate-time unit, ramp-rate, segment
PID group numbers, operation at the time of segment
switching, wait operation type, and wait numbers.
Wait action setting:
Set wait zone off/on, wait zone settings, and timer.
Event setting:
Set event types, loop number/type/setpoint (only when
PV event is selected), time event ON/OFF, ON time/OFF
time (only when time event is selected) and hysteresis of
PV event.
Event output setting:
Set the event type, relay output ON/OFF, and relay
output number.
Repeat action setting:
Set the repeat function, number of repetitions, start
segment number, and end segment number.
Auto message printing/
program display position
setting
→ Section 1.11
1.2 Control Function Overview