Standard installation environment – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 366
14-18
IM 04L31A01-01E
Standard Installation Environment
Standard operating conditions:
Ambient temperature: 0 to 50 °C (5 to 40 ° C when floppy disk or Zip disk is in operation)
Ambient humidity:
20 to 80% RH (at 5 to 40 °C)
Vibration:
10 to 60 Hz 0.2 m/s
2
Shock:
Not allowed
Magnetic field:
400 A/m or less (DC and 50/60 Hz)
External noise:
Normal mode (50/60 Hz)
Volt: The peak value including the signal must be less than
1.2 times the measuring range.
TC: The peak value including the signal must be less than
1.2 times the measuring thermal electromotive force.
RTD: 50 mV or less
Common mode noise (50/60 Hz):
250 Vrms AC or less for all ranges
Maximum noise voltage between channels (50/60 Hz):
250 Vrms AC or less
Mounting position:
Up to 30° of backward tilt angle allowed, no tilt to the left or right
Warm-up time:
At least 30 minutes after power-up
Altitude:
2000 m or less
Transport and storage conditions:
Ambient temperature: –25 to 60 °C
Humidity:
5 to 95%RH (no condensation)
Vibration:
10 to 60 Hz 4.9 m/s
2
Shock:
392 m/s
2
or less (packaged condition)
Safety and EMC Standards
Safety
CSA:
Certified by CSA22.2 No. 61010.1, Installation category II
*1
,
Pollution degree 2
*2
, Measurement category II
*3
UL:
Certified by UL61010-1 (CSA NRTL/C)
CE:
Complies with EN61010-1
*
1 “Installation category (Overvoltage category)” describes a number which defines a transient
overvoltage condition. It implies the regulation for impulse withstand voltage. “II” applies to
electrical equipment which is supplied from the fixed installation like distribution board.
*
2 “Pollution degree” describes the degree to which a solid, liquid, or gas which deteriorates
dielectric strength or surface resistivity is adhering. “2” applies to normal indoor atmosphere.
Normally, only non-conductive pollution occurs.
*
3 Applies to measuring circuits connected to low voltage installation, and electrical instruments
supplied with power from fixed equipment such as electric switchboards.
EMC Conformity standards
Altitude:
2000 m or less
CE:
EN61326-1 Class A, Table 2 (For use in industrial locations)
EN61326-2-3
EN55011 Class A, Group1
EN61000-3-2 Class A
EN61000-3-3
C-tick:
EN55011 Class A, Group1
The instrument continues to operate at a measurement accuracy of within ±10% of
the range during testing.
Power Supply
Supply voltage:
100 to 110 VAC±10%, 200 to 220 VAC±10%
Power frequency:
50 Hz ± 2%, 60 Hz ± 2%
Power consumption:
Supply Voltage
100 VAC
240 VAC
LCD Saver Mode
Approx. 43 VA
Approx. 62 VA
Normal
Approx. 45 VA
Approx. 65 VA
Max.
75 VA
106 VA
* For the power supply specifications when the CX1000 is driven by the 24-V power
supply, see “24 VDC/AC power supply driven (/P1)” in section 14.7, “Options.”
14.8 General Specifications